How to Select a Frequency Converter: A Buyer's Guide

How to Select a Frequency Converter: A Buyer’s Guide

To select a frequency converter, start with the load rather than the datasheet. Identify what it will feed, apply the sizing rule for that load type, choose single or three phase, set capacity and overload, match the unit to the site, and write the result as a specification. Most bad purchases skip the first step entirely.

Mark Reyes ran maintenance at a stamping plant in Ohio that needed 60 Hz power for a press imported from Europe. The electrician totaled the connected load at 40 kVA and bought a 45 kVA solid-state converter, a sensible-looking 12 percent margin. The press tripped it on every start.

A hard-starting motor draws five to seven times rated current for up to two seconds; the converter’s overload covered milliseconds. Nobody had asked what the load was.

If you are still deciding which device family you need, the AC frequency converter types guide sets that out first. This article assumes you need a converter and must specify one.

Key Takeaways

  • Load type sets the sizing rule. A resistive load needs about 10 percent margin; a hard-starting motor can need six times its rating.
  • Rectifier and switch-mode loads are sized on crest factor, not average current. A unit sized on nameplate kVA will trip.
  • Solid-state converters cannot tolerate loads that feed distortion back, such as welders and SCR heaters, unless the distortion is isolated.
  • Capacity is quoted at 40 °C. Above that, expect roughly 2 percent of load lost per degree.
  • The output of selection is a specification, not a product choice. Twelve fields settle most enquiries.

Not sure what your load draws? Our engineers review load lists and motor nameplates routinely. Send us the details and we will check the sizing before you order.

How to Select a Frequency Converter in Six Steps

How to Select a Frequency Converter in Six Steps
How to Select a Frequency Converter in Six Steps

Work through these in order. Each narrows the field before the next.

  1. Identify the load type. Resistive, capacitive, motor, rectifier, regenerative or mixed. This answer sets the sizing rule, the overload requirement, and whether a solid-state unit is suitable at all.
  2. Confirm the device family. A motor whose speed you control wants a variable frequency drive. A fixed output frequency for a panel of mixed loads wants a static converter, where static frequency converter selection turns on load category rather than motor data.
  3. Choose single or three-phase. Single-phase caps capacity and raises input current. Three-phase is the default above a few kVA.
  4. Set capacity, margin and overload. Convert the load to kVA, apply its rule, then add margin. Frequency converter capacity is quoted at a temperature and an overload duration, so check both to cover your surge.
  5. Match the unit to the site. Ambient temperature, altitude, dust, humidity and the enclosure rating the plant room needs.
  6. Write the specification. Voltage, frequency, capacity, duty, overload, waveform, enclosure, interface and standards, in a form a supplier can price without guessing.

Frequency Converter Load Types and What Each One Demands

Frequency Converter Load Types and What Each One Demands
Frequency Converter Load Types and What Each One Demands

Frequency converter load types behave differently enough that no single rule covers them. The table is the short version; the subsections explain why each rule exists.

Load type Sizing rule Why
Resistive 1.1 × load power Current and voltage stay in phase; almost no surge
Capacitive / RC 1.1 × load apparent power Charging current leads the voltage, so VA exceeds W
Motor (hard start) About 6 × motor power, or fit a soft starter Starting current is 5-7 × rated for up to 2 seconds
Rectifier / switch-mode Crest factor ÷ 2 × apparent power, when crest factor exceeds 2 Pulsed current peaks far above its average
Regenerative Standard sizing, but declared at order Back EMF can damage the output stage
Mixed Each load’s share of total power, then sum The dominant load sets the behaviour

These are manufacturer rules of thumb, not standard requirements. GoHz publishes the set most other vendors repeat.

Resistive loads: the easy case

Heaters, incandescent lighting and resistive test banks draw current in phase with voltage. There is no inrush and no distortion to manage. A 10 percent margin covers supply variation and the fact that a converter’s rating is measured on a resistive load anyway. Plants routinely buy two or three times the capacity they need because the rule they learned came from motors.

Capacitive and RC loads: apparent power, not real power

A capacitive load draws current that leads the voltage, so apparent power in volt-amperes exceeds real power in watts. Size on the VA figure, not the nameplate wattage. A load rated 10 kW at a power factor of 0.8 presents 12.5 kVA, and the converter must carry all of it.

Motor loads: inrush is the whole problem

A motor started direct-on-line draws five to seven times its rated current, typically for under two seconds. A converter’s overload capability is usually around 200 percent, lasting milliseconds before protection trips. Those two facts do not meet, so a converter sized at the motor’s running kVA trips on every start.

However, you have three options, and only one involves buying a bigger converter:

  • Oversize to about six times motor power. Works, but you pay for capacity used two seconds a day.
  • Fit a soft starter upstream. Removes the inrush, so the converter sizes normally.
  • Fit a variable frequency drive on the motor. The drive ramps the motor under control and removes the problem at source. For a single motor, how to select a VFD covers that properly.

The third is usually the cheapest, and the one buyers overlook.

Rectifier and switch-mode loads: crest factor decides

This load type most often produces a converter that trips for no visible reason.

A rectifier front end with a capacitor bank draws current in short, tall pulses near the voltage peaks. Without soft-start upstream, closing the input looks like a short circuit and the converter’s overcurrent protection operates at once. The pulses also mean peak current sits far above average. Crest factor is peak divided by RMS current, and a clean sine wave sits near 1.4 while a rectifier load typically reaches 3 to 3.5.

Converter output stages respond to peak current, not average. Therefore a unit sized on average kVA is undersized in the only dimension that matters:

Capacity = (crest factor ÷ 2) × load apparent power

A load at crest factor 3.2 drawing 20 kVA needs 32 kVA. Ask the equipment supplier for the crest factor. If they cannot provide it, measure the input waveform before ordering.

Regenerative loads: declare them

Reversing motors, overhauling loads and anything pushing energy back toward the supply generate a back EMF that can damage a converter’s output stage. The fix is not a sizing rule but disclosure. Tell the supplier at the enquiry stage that the load regenerates, and let them specify a unit that absorbs or blocks it. A converter chosen without that information may work for months and fail the first time the load overhauls hard.

Mixed loads: weight by share

Real panels are rarely one load type. A machine might carry a motor, a heater, a switch-mode supply and a control transformer. Total each load’s share of the power, size the dominant load by its own rule, and add the rest. The dominant load sets the behaviour: a motor means inrush governs, a rectifier means crest factor governs.

The distorting-load trap nobody warns you about

Every rule above assumes the converter can supply the load. Some loads it cannot, at any size.

Solid-state converters are not suitable for loads that feed distortion back into the line: silicon-controlled rectifiers, triacs, IGBT front ends, phase-angle dimmers and welders. The output stage assumes it is driving the waveform, and these loads fight it. Visicomm states the limitation directly, noting such loads are acceptable only where distortion can be isolated.

Two honest answers exist. Isolation and filtering, if the distortion is bounded and the budget allows. Alternatively, a rotary converter, a motor driving a generator, is indifferent to the load because the generator’s inertia absorbs it. Rotary sets also isolate the load from the rest of the plant supply.

This is where Aisha Karim, who ran the electrical workshop at a fabrication shop in Sheffield, lost three months. The shop bought a 30 kVA solid-state converter for an imported resistance welder rated 28 kVA, so 30 kVA looked correct. It tripped on almost every weld, because a resistance welder is a phase-angle load whose current waveform is nothing like a sine wave.

The fix was a rotary set, at roughly twice the price and eight weeks of lead time. The nameplate figure was accurate; it was also the wrong number.

To spot one before you specify, ask three questions. Does the load switch its current within a cycle rather than following the voltage waveform, as dimmers, welders and SCR heaters do? Does it have a rectifier and capacitor bank at its input, as most modern electronics do? Does it ever push energy back toward the supply, as reversing drives and overhauling hoists do?

A yes to the first or third puts you in rotary or isolated territory. A yes to the second means you need the crest factor, not a rotary set.

How to Select a Frequency Converter for Single or Three Phase

How to Select a Frequency Converter for Single or Three Phase
How to Select a Frequency Converter for Single or Three Phase

Choosing a frequency converter with the wrong phase is rarely fatal, but it constrains capacity in ways worth knowing.

Single-phase units suit light loads, test benches and sites without three-phase power. They are simple and cheap at low ratings. The constraint is current: a single-phase unit carries three times the current per conductor for the same power, which drives cable size, terminal ratings and losses. In practice most top out in the low tens of kVA.

Above roughly 20 to 30 kVA, three-phase stops being a preference. It also matters for balance, since a large single-phase load on one phase creates voltage unbalance that affects every other load on the board. Piller’s published range shows the pattern: static units 30 kVA to 500 kVA, rotary sets 125 kVA to 2,300 kVA, all three-phase products.

If your load is above about 30 kVA and the site has three-phase power, specify three-phase and move on.

Match the Specification to the Site

A converter rated for its capacity at 40 °C in a clean electrical room is not the same product in a foundry at 48 °C. Datasheet figures are conditional, and the conditions are stated.

Ambient temperature and the derate above 40 °C

ABB’s PCS100 is rated 0 °C to 40 °C, with derating of 2 percent of load per degree above 40 °C up to a 50 °C maximum. That shape is typical, though the slope varies by product. A 100 kVA unit in a 45 °C plant room delivers about 90 kVA. Consequently, a unit installed at nameplate in a hot room runs at its thermal limit continuously, shortening capacitor and fan life whether or not it trips.

Tomás Ferreira inherited exactly this at a Portuguese ceramics plant. A 60 kVA converter had been installed at nameplate in a room peaking at 46 °C. It failed twice in fourteen months, both times in August.

The replacement was specified at 75 kVA with the derate applied, and has run for three years. The failure was never a manufacturing defect; the specification ignored the room.

Altitude above roughly 1,000 m

Air thins with altitude, so convective cooling degrades. Above about 1,000 m most manufacturers require derating, and the slope varies enough that you should ask rather than assume. A plant at 2,000 m may need 10 percent more capacity.

Enclosure and IP rating

Match the enclosure to the room, not to the catalogue’s cheapest option.

Environment Typical rating Notes
Clean, climate-controlled electrical room IP20 Open-frame or cabinet, forced air
General factory floor IP54 Dust-tight and splash-resistant
Washdown, food, outdoor sheltered IP65 Sealed; check the cooling path
Corrosive or coastal IP65 plus conformal coating Ask specifically about coating

A sealed enclosure solves ingress and creates a thermal problem at once. An IP65 unit in a hot room may need an air-conditioned cabinet or heat exchanger, which changes installation cost. Raise it at specification, not commissioning.

Overload capacity and what the percentage buys

Overload is quoted as a percentage for a duration, and both parts matter. ABB’s PCS100 offers 120 percent for 10 minutes at 75 percent pre-load, and 150 percent for 30 seconds. The 10-minute figure covers a sustained overload; the 30-second figure covers a start. Neither covers a hard-starting motor at 600 percent for two seconds, which is why motor loads need the sizing treatment above rather than a bigger overload number.

Write the Frequency Converter Specification Suppliers Can Quote Against

Write the Frequency Converter Specification Suppliers Can Quote Against
Write the Frequency Converter Specification Suppliers Can Quote Against

Frequency converter selection ends with a document, not a decision. A supplier with all twelve fields below can price without guessing.

The twelve fields every enquiry needs

  1. Input voltage and phase, including the tolerance your supply actually shows.
  2. Input frequency, and whether the site is stable or subject to generator operation.
  3. Output voltage, and whether it must be adjustable.
  4. Output frequency, and critically whether the unit is rated to deliver full power there continuously. A converter that can be set to 400 Hz is not necessarily one that can run there at full load.
  5. Capacity in kVA, with the load type that produced the figure.
  6. Load description, including whether it is distorting or regenerative.
  7. Duty cycle: continuous, intermittent, or a stated pattern.
  8. Overload requirement, as a percentage and a duration.
  9. Output waveform quality, as a maximum distortion figure your most sensitive load accepts.
  10. Ambient temperature, altitude and enclosure rating for the installed location.
  11. Interface and communications: what the unit must accept and report, and to which system.
  12. Standards and certification the installation must meet, and the documentation the project requires.

Field four is the one buyers most often omit. A unit rated 100 kVA at 50 Hz may be rated considerably lower at 400 Hz, so put the per-frequency rating in the enquiry and answers come back comparable.

Interface, control and communications

Decide what the converter must do besides convert. Remote start and stop, status reporting, alarm contacts and metering all change the specification and the price. Protocol matters if the unit joins a plant network: Modbus is close to universal, while Profinet and EtherNet/IP are common in European and North American plants. If it will be monitored from SCADA, say so; that changes the option cards.

What to ask before you compare prices

Four questions separate a comparable quote from a cheap one:

  • Is the capacity quoted at 40 °C or at your site temperature?
  • What is the overload rating, and for how long?
  • What is the output distortion at full load, into a linear load?
  • What is the service interval, and are wear parts available locally?

A quote that answers all four is a specification. One that answers none is a price. For the drive-side equivalent, our VFD specification template sets out the same field list. If the application needs conversion between grids rather than a fixed output, converting equipment between 50 Hz and 60 Hz covers that case directly.

Frequently Asked Questions

How do I select a frequency converter for a motor load?

Size at roughly six times the motor’s rated power if it starts direct-on-line, because starting current runs five to seven times rated for up to two seconds while the converter’s overload lasts milliseconds. Better, fit a soft starter or a variable frequency drive so the inrush never reaches the converter.

What size frequency converter do I need?

Convert the load to kVA, then apply its rule: about 1.1 times for resistive loads, 1.1 times apparent power for capacitive loads, and crest factor divided by two times apparent power for rectifier loads. Then derate for site temperature and altitude.

Can a frequency converter run a welder?

Usually not a solid-state one. Welders are phase-angle loads that feed distortion back into the line, and solid-state converters cannot handle them unless the distortion is isolated and filtered. A rotary set takes the load without difficulty.

What is crest factor and why does it matter?

Crest factor is peak current divided by RMS current. A sine wave sits near 1.4; a rectifier load typically reaches 3 to 3.5. Converter output stages respond to peak current, so a unit sized on average kVA is undersized for a high-crest-factor load.

How much margin should I add?

Manufacturers commonly suggest 20 to 30 percent above steady-state load to cover supply variation and startup surge. That assumes the load type has already been handled by its own rule.

What is the difference between rated and settable frequency?

A settable frequency is one the unit can be configured to produce. A rated frequency is one at which it delivers full power continuously. Many converters offer roughly 10 to 400 Hz adjustable, but the kVA rating at the top of that range is usually lower than at 50 or 60 Hz.

How to Select a Frequency Converter That Matches the Load

Frequency converter selection comes down to six decisions, and the first carries most of the weight. A clear set of frequency converter selection criteria makes the rest mechanical.

  • The load type sets the rule. Resistive loads need 10 percent margin; a hard-starting motor may need six times its rating.
  • Crest factor governs rectifier loads. Ask for the number or measure the waveform.
  • Some loads need a different device, not a bigger one. Distorting loads want isolation or a rotary set; a single speed-controlled motor wants a drive.
  • Capacity is conditional on the site. A 40 °C rating in a 45 °C room is not the rating you bought.
  • Overload is a percentage and a duration. Both must cover the surge you actually have.
  • The output is a specification. Twelve fields turn a price into a comparable quote.

The expensive mistakes come from starting at the datasheet, where every unit looks capable of every job.

If your project involves motors on a converted or controlled supply, the drive side matters as much as the converter. Shandong Electric builds variable frequency drives from compact low voltage units to high voltage systems for heavy industry, with engineering support from selection through commissioning. Where the load turns out to be a speed-controlled motor, the frequency converter types guide explains which device that changes. Tell us about your load and we will help you match the right equipment to the application.

Leave a Reply

Your email address will not be published. Required fields are marked *